Programming Your Application
6-25
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::I2P Menu
I2T INHIBIT
Inhibit/enable the action of the motor protection.
0=FALSE
1=TRUE
FALSE
I2T LIMIT MOTOR
This is diagnostic information:
0 : motor load level is lower than 100%
1 : motor load level is higher than 100%
0/1
I2T LIMIT LOAD
This is a diagnostic information.
Indicates the percentage of motor load. This value is based on PERM
CURRENT (permanent motor current). The time variation is based on
THERMAL TIM CST
---%
I2T MOTOR TRIP
State of the I2T trip, reported as MOTOR OVERTEMP:
0: the motor is running, the motor load level is lower than 100%
1: the motor is stopped; the motor load level is higher than 100%
0=FALSE
1=TRUE
SET::POL Menu
POLARISATION
Set this parameter to enter the motor polarisation mode
Clear it for standard SV control mode
0=FALSE
1=TRUE
POLAR START
Set this parameter to enable the motor polarisation mode
Clear it to disable the motor polarisation mode
0=FALSE
1=TRUE
MOTOR PHASE
Select on which motor phases the motor polarisation is applied.
When the motor polarisation is enabled, changing the motor phase
allows to rotate the motor like a stepper motor.
That gives the possibility to verify the correct motor phase connection to
get a clockwise direction for a positive speed setpoint
0=U PHASE
1=V PHASE
2=W PHASE
CURRENT
This diagnostic gives the current setpoint applied to the motor during the
motor polarisation mode.
---A
SET::POS Menu
START
A False to True transition starts the move command.
0=FALSE
1=TRUE
ABORT
When True the ongoing move is aborted (null speed set-point) and no
further move command can be started.
0=FALSE
1=TRUE
TARGET
Specify the move command target. Depending of the move type it is an
absolute, a relative or a travel distance.
-32768 to 32768
0