9-6
Technical Specifications
650S AC Drive
Electrical Ratings
Motor power, output current and input current must not be exceeded under steady state operating
conditions.
Maximum Motor dv/dt = 10,000V/
μ
s. This can be reduced by adding a motor choke in series with
the motor. Contact Parker SSD Drives for recommended choke details.
Local wiring regulations always take precedence. Select cable rated for the drive.
The supply must be protected with a fuse (or Type B RCD) rated to the supply cable.
FRAME 3 : 1-Phase (IT/TN), 230V
Drive Power
(kW/hp)
Input Current @ 7.5kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power Loss
(W)
2.2/3.0 22.0
9.6
112
FRAME 3 : 3-Phase (IT/TN), 230V
Drive Power
(kW/hp)
Input Current @ 7.5kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power Loss
(W)
2.2/3.0 14.3
9.6
103
3.0/4.0 18.1
12.3
133
4.0/5.0 23.1
16.4
180
FRAME 3 : 3-Phase (IT/TN), 400V
Drive Power
(kW/hp)
Input Current @ 10kA
(A)
Output Current @ 40
o
C
(A) ac
Maximum Power Loss
(W)
3.0/4.0 11.1
6.8
80
4.0/5.0 13.9
9.0
100
5.5/7.5 18.0
12.0
136
7.5/10.0 23.6
16.0
180