Programming Your Application
6-31
650S AC Drive
Configure for use as a Digital Output
For example, to use terminal 10 as an output, select DOUT 2 SOURCE to be 1, 2, 3, 4 , 5 or 6. For instance, you could set
parameter DOUT 2 SOURCE to 3 to have the output go high (24V) whenever the motor is running, operating an external
relay or lamp. You can invert this logic using parameter DOUT 2 INVERT.
Parameter
Setting
The output is high when:
1 = HEALTH
The Run signal is not present, or no trip is active
2 = TRIPPED
A trip is present
3 = RUNNING
The motor is running
4 = AT ZERO
The output frequency is below 1% of MAX SPEED (
P
2)
5 = AT SPEED
The output frequency is at or near Setpoint and within ±1% of MAX
SPEED, set by (P2).
6 = AT LOAD
DOUT2 SOURCE
Always set DIN 4 INVERT to 0 if using Applications 1 and 5 – refer to Chapter 12.
DOUT2 INVERT
Default is 0, setting to 1 inverts the output logic