3-8
Installing the Drive
650S AC Drive
Power Wiring Connections
Terminal
Description
Function
Range
200V 1-Phase
200V/400V 3-Phase
TH1A Thermistor
Connection
to
motor thermistor
TH1B Thermistor
Connection
to
motor thermistor
It is good practice to protect motors by fitting temperature
sensitive resistors. A typical resistance (up to a reference
temperature of 125
°
C) is 200
Ω
, rising rapidly to 2000
Ω
above this temperature. Connect devices in series between
TH1A and TH1B. Link the terminals if temperature sensors
are not used.
Reference
Terminal
Supply protective earth (PE). This terminal must be connected to a protective
(earth) ground for permanent earthing.
L1
Power Input
Single and three
phase live
connection
220/240V ac ±10% rms
with respect to L2/N. 50-
60Hz (IT/TN)
220/240V or 380/460V ac ±10%
rms with respect to L2, L3 phase-
to-phase. 50-60Hz (IT/TN)
L2/N
L2
Power Input
Single phase neutral
(or L2 three phase
live connection)
220/240V ac ±10% with
respect to L1. 50-60Hz
(IT/TN)
220/240V or 380/460V ac ±10%
with respect to L1, L3. 50-60Hz
(IT/TN)
L3
Power Input
Three phase live
connection
Not applicable
220/240V or 380/460V ac ±10%
with respect to L1, L2. 50-60Hz
(IT/TN)
DC-
No user connection
DC+
Dynamic Brake Connection to
external brake
resistor
Not applicable
Frame 2 (high volt only) & 3.
See “Internal Dynamic Brake
Switch” table
DBR
Dynamic Brake Connection to
external brake
resistor
Not applicable
Frame 2 (high volt only) & 3.
See “Internal Dynamic Brake
Switch” table
M1/U
M2/V
M3/W
Motor Outputs
Connection for
motor
Motor rated at:
0 to 220/240V ac
0 to 500Hz
Motor rated at:
0 to 220/240V or 0 to 380/460V
ac 0 to 500Hz
Reference
Terminal
Supply protective earth (PE). This terminal must be connected to a protective(earth)
ground for permanent earthing.