6-6
Programming Your Application
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
AIN 2 SCALE
-300.0 to 300.0%
100.0%
AIN 2 OFFSET
-300.0 to 300.0%
0.0%
AIN 2 TYPE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
0= 0-10V
1= 0-5V
2= 0-20mA
3= 4-20mA
3
SET::OUT Menu
DOUT 1 INVERT
Inverts the value of the signal, TRUE or FALSE.
0= FALSE
1= TRUE
0
DOUT 2 INVERT
Inverts the value of the signal, TRUE or FALSE.
0= FALSE
1= TRUE
0
RELAY INVERT
Inverts the value of the signal, TRUE or FALSE.
0=FALSE
1=TRUE
0
AOUT 1 SCALE
-300.00 to 300.00% 100.00%
AOUT 1 OFFSET
-300.00 to 300.00% 0.00%
AOUT 1 ABSOLUTE
+
SCALE
OFFSET
X
VALUE
ABS
X
OUTPUT
100%
0%
CLAMP
0= FALSE
(not absolute)
1= TRUE (absolute)
1
AOUT 2 SCALE
-300.00 to 300.00% 100.00%
AOUT 2 OFFSET
-300.00 to 300.00% 0.00%
AOUT 2 ABSOLUTE
+
SCALE
OFFSET
X
VALUE
ABS
X
OUTPUT
100%
0%
CLAMP
0= FALSE
(not absolute)
1= TRUE (absolute)
1