Installing the Drive
3-9
650S AC Drive
Terminal Block Acceptance Sizes
Wire sizes should be chosen with respect to the operating conditions and your local National Electrical Safety Installation
Requirements. Local wiring regulations always take precedence.
Frame Size
Power Terminals
(maximum wire size)
Brake Terminals
(maximum wire size)
Thermistor/Control Terminals
(maximum wire size)
Frame 1
230V
2.5mm
2
/12 AWG
Not Applicable
2.5mm
2
/12 AWG
Frame 2
230V
2.5mm
2
/12 AWG
Not Applicable
2.5mm
2
/12 AWG
Frame 2
400V
2.5mm
2
/12 AWG
2.5mm
2
/12 AWG
2.5mm
2
/12 AWG
Frame 3
230V
6.0mm
2
/10 AWG
6.0mm
2
/10 AWG
2.5mm
2
/12 AWG
Frame 3
400V
6.0mm
2
/10 AWG
6.0mm
2
/10 AWG
2.5mm
2
/12 AWG
Power Wiring
Note:
For specified EMC emission and immunity performance, install to EMC Installation Instructions. Refer to Chapter
10: “Certification for the Drive” - for more information
Terminal tightening torque for Frame 3 power connections is 20 lb.in (2.26Nm).
Protect the incoming mains supply using the specified fuse, or RCD circuit breaker Type B.
IMPORTANT:
We do not recommend the use of circuit breakers (e.g. RCD, ELCB, GFCI), however, where their use is mandatory, they
must:
•
Operate correctly with dc and ac protective earth currents (i.e. type B RCDs as in Amendment 2 of IEC755).
•
Have adjustable trip amplitude and time characteristics to prevent nuisance tripping on switch-on.