9-48
AC10 Inverter
FC22
Forward speed limited channel
0: Digital given (FC23)
(adjust with keypad)
1: Analog input AI1
2: Analog input AI2
0
FC23
Forward speed limited (%)
0
~
100.0
10.0
FC24
Reverse speed limited channel
0: Digital given (FC25)
(adjust with keypad)
1: Analog input AI1
2: Analog input AI2
0
FC25
Reverse speed limited (%)
0
~
100.0
10.00
Speed limited FC23/FC25: if given speed reaches max value, they are used to set percent of
inverter output frequency and max frequency F111.
FC28
Driving torque limit reference
source
0: Digital given (FC30)
(adjust with keypad)
1: Analog input AI1
2: Analog input AI2
0
FC29
Driving torque limit coefficient
0
~
3.000
3.000
FC30
Driving torque limit (%)
0
~
300.0
200.0
FC31
Re-generating torque limit channel
0: Digital given (FC35)
(adjust with keypad)
1: Analog input AI1
2: Analog input AI2
0
FC34
Re-generating torque limit
coefficient
0
~
3.000
3.000
FC35
Re-generating torque limit (%)
0
~
300.0
200.00
When motor is in the driving status, output torque limit channel is set by FC28, and limit torque
is set by FC29.
When motor is in the re-generating status, re-generating torque limit channel is set by FC31,
and limit torque is set by FC34.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...