AC10 Inverter
F210 Frequency display
accuracy
Setting range:
0.01
~
2.00
Mfr’s value: 0.01
Under keypad speed control or terminal UP/DOWN speed control, frequency display accuracy
is set by this function code and the range is from 0.01 to 2.00. For example, when F210=0.5,
▲
/
▼
terminal is pressed at one time, frequency will increase or decrease by 0.5Hz.
F211 Speed of digital control
Setting range:
0.01
~
100.0Hz/S
Mfr’s value: 5.00
When UP/DOWN terminal is pressed, frequency will change at the setting rate. The Mfr’s
value is 5.00Hz/s.
F212 Direction memory
Setting range:
0: Disable
1: Enable
Mfr’s value: 0
This function is valid when three-line operation mode 1(F208=3) is valid.
When F212=0
,
after inverter is stopped, reset and repowered on, the running direction is not
memorized.
When F212=1
,
after inverter is stopped, reset and repowered on, if inverter starts running but
no direction signal, inverter will run according the memory direction.
F213 Auto-starting after
repowered on
Setting range:
0: Disable
1: Enable
Mfr’s value: 0
F214 Auto-starting after reset
Setting range:
0: Disable
1: Enable
Mfr’s value: 0
Whether or not to start automatically after repowered on is set by F213
F213=1, Auto-starting after repowered on is valid. When inverter is power off and then
powered on again, it will run automatically after the time set by F215 and according to the
running mode before power-down. If F220=0 frequency memory after power-down is not valid,
inverter will run by the setting value of F113.
F213=0, after repower-on, inverter will not run automatically unless running command is given
to inverter.
Whether or not to start automatically after fault resetting is set by F214
When F214=1, if fault occurs, inverter will reset automatically after delay time for fault reset
(F217). After resetting, inverter will run automatically after the auto-starting delay time (F215).
If frequency memory after power-down (F220) is valid, inverter will run at the speed before
power-down. Otherwise, inverter will run at the speed set by F113.
In case of fault under running status, inverter will reset automatically and auto-start. In case of
fault under stopped status, the inverter will only reset automatically.
When F214=0, after fault occurs, inverter will display fault code, it must be reset manually.
F215 Auto-starting delay time
Setting range:
0.1
~
3000.0
Mfr’s value: 60.0
F215 is the auto-starting delay time for F213 and F214. The range is from 0.1s to 3000.0s.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...