8-6
AC10 Inverter
v.
Press the “I” key, to start the inverter;
vi.
During running, current frequency of the inverter can be changed by pressing ▲ or
▼;
vii.
Press the “O” key once, the motor will decelerate until it stops running;
viii.
Switch off the main switch, and power off the inverter.
8.3.2 Setting the frequency using the keypad panel, and starting, forward and reverse
running, and stopping inverter through control terminals
i.
Connect the wires in accordance with
. After having checked the wiring
successfully, switch on the main switch, and power on the inverter;
Figure 8-2
Wiring Diagram 2
ii.
Press the “M” key, to enter the programming menu.
iii.
Study the parameters of the motor: the operation process is the same as that of
example 1. (Refer to 8.3.1 for tuning of the motor).
iv.
Set functional parameters of the inverter:
Function code
Parameter
Values
F111
Maximum frequency
50.00
F203
Main frequency source
0
F208
Terminal operational mode
1
v.
Close the switch DI3, the inverter starts forward running;
vi.
During running, current frequency of the inverter can be changed by pressing ▲ or
▼;
vii.
During running, switch off the switch DI3, then close the switch DI4, the running
direction of the motor will be changed (Note: The user should set the dead time of
forward and reverse running F120 on the basis of the load. If it was too short, OC
protection of the inverter may occur.)
viii.
Switch off the switches DI3 and DI4, the motor will decelerate until it stops running;
ix.
Switch off the main switch to power off the inverter.
8.3.3 Operation process of jogging operation using the keypad panel
i.
Connect the wires in accordance with Figure 8-1. After having checked the wiring
successfully, switch on the isolator, and power on the inverter;
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...