AC10 Inverter
F732 Under-voltage threshold (V)
Setting range: 0~450
Subject to
inverter model
“Under-voltage” refers to too low voltage at AC input side.
“Input phase loss” refers to phase loss of three-phase power supply, 5.5 kW and below
inverters have not got this function.
“Output phase loss” refers to phase loss of inverter three-phase wirings or motor wirings.
·““Phase loss” signal filtering constant is used for the purpose of eliminating disturbance to
avoid mis-protection. The greater the set value is, the longer the filtering time constant is and
the better for the filtering effect.
F737 Over-current 1 protection
Setting range:
0: Disabled
1: Enabled
Mfr’s value: 1
F738 Over-current 1 protection coefficient Setting range: 0.50
~
3.00
Mfr’s value:
2.50
F739 Over-current 1 protection record
F738= OC 1 value/inverter rated current.
In running status, F738 is not allowed to modify. When over-current occurs, OC1 is displayed
F741 Analog disconnected protection
Setting range:
0: Disabled
1: Stop and AErr displays.
2: Stop and AErr is not displayed.
3: Inverter runs at the min
frequency.
4: Reserved.
Mfr’s value: 0
F742 Threshold of analog disconnected
protection (%)
Setting range: 1~100
Mfr’s value: 50
When the values of F400 and F406 are lower than 0.01V, analog disconnected protection is
invalid.
When F741 is set to 1, 2 or 3, the values of F400 and F406 should be set to 1V-2V, to avoid
the error protection by interference.
Analog disconnected protection voltage=analog channel input lower limit * F742. Take the AI1
channel for the example, if F400=1.00, F742=50, then disconnection protection will occur
when the AI1 channel voltage is lower than 0.5V.
F745 Threshold of pre-alarm overheat (%) Setting range: 0~100
Mfr’s value: 80
F747 Carrier frequency auto-adjusting
Setting range:
0: Disabled
1: Enabled
Mfr’s value: 1
When the temperature of the heatsink reaches the value of 95
℃
X F745 and multi-function output
terminal is set to 16 (refer to F300~F302), it indicates inverter is in the status of overheat, and
when F747=1, the temperature of the heatsink reaches 86
℃
, inverter carrier frequency will
adjust automatically, to decrease the temperature of inverter. This function can avoid overheat
malfunction.
When F159=1, random carrier frequency is selected, F747 is disabled.
When F106=6, carrier frequency auto adjusting function is disabled.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...