14-2
Compliance
AC10 Inverter
14.2 European Compliance
CE Marking
The CE marking is placed upon the product by Parker Hannifin Manufacturing Ltd to facilitate
its free movement within the European Economic Area (EEA). The CE marking provides a
presumption of conformity to all applicable directives. Harmonized standards are used to
demonstrate compliance with the essential requirements laid down in those relevant
directives.
It must be remembered that there is no guarantee that combinations of compliant components
will result in a compliant system. This means that compliance to harmonised standards will
have to be demonstrated for the system as a whole to ensure compliance with the directive.
14.2.1 Low Voltage Directive
When installed in accordance with this manual the product will comply with the low voltage
directive 2006/95/EC.
Protective Earth (PE) Connections
Only one protective earth
conductor is permitted at each protective earth terminal
contacting point.
The product requires a protective earth conductor cross section of at least 10mm², where this
is not possible a second protective ground terminal provided on the VSD (Variable Speed
Drive) shall be used. The second conductor should be independent but electrically in
parallel.
14.2.2 EMC Directive
When installed in accordance with this manual the product will comply with the electromagnet
compatibility directive 2004/108/EC.
The following information is provided to maximise the Electro Magnetic Compatibility (EMC) of
VSDs and systems in their intended operating environment, by minimising their emissions and
maximising their immunity.
14.2.3 Machinery Directive
When installed in accordance with this manual the product will comply with the machinery
directive 2006/42/EC.
This product is classified under category 21 of annex IV as ‘logic units to ensure safety
functions’. All instructions, warnings and safety information can be found in Chapter 6.
This product is a component to be incorporated into machinery and may not be operated
alone. The complete machinery or installation using this equipment may only be put into
service when all safety considerations of the Directive are fully implemented. Particular
reference should be made to EN60204-1 (Safety of Machinery - Electrical Equipment of
Machines).
14.2.4 EMC Compliance
WARNING
In a domestic environment, this product may cause radio interference, in which case
supplementary mitigation measures may be required.
Local wiring regulations always take precedence.
Where there are any conflicts between regulatory standards for example
earthing requirements for electromagnetic compatibility, safety shall always
take precedence.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...