4-1
AC10 Inverter
Chapter 4
Maintenance
4.1 Periodic Checking
Cooling fan and ventilation channel should be cleaned regularly to check it is clear; remove
any dust accumulated in the inverter on a regular basis.
Check inverter’s input and output wiring and wiring terminals regularly and check if wirings are
ageing.
Check whether screws on each terminals are fastened.
4.2 Storage
Store the inverter in the original packing case.
If the inverter is stored for long time, power the inverter at minimum intervals of 6 months to
prevent the electrolytic capacitors being damaged. The inverter should be powered up for
longer than 5 hours. If the inverter is stored for longer than 18 months without powering it up,
the capacitors will have to be reformed or damage may occur to the inverter when power is
applied.
4.3 Daily Maintenance
Environment temperature, humidity, dust and vibration would decrease the life of inverter. Daily
maintenance is necessary to inverters.
Daily inspecting:
Inspect the motor for unusual noise when it is operating.
Inspect for abnormal vibration of the motor when it is operating.
Inspect the environmental operating conditions of the inverter.
Inspect for proper operation of the fan and inverter temperature.
Daily cleaning:
Keep the inverter clean. Clean surface dust of inverter to prevent dust, metal powder, oily dirt
and water from dropping into the inverter.
4.4 Returning the Unit to Parker SSD Drives
Please have the following information available:
• The model and serial number - see the unit’s rating label
• Details of the fault
Contact your nearest Parker SSD Drives Service Center to arrange return of the item.
You will be given a
Returned Material Authorization.
Use this as a reference on all paperwork
you return with the faulty item. Pack and return the item in the original packing materials; or at
least an anti-static enclosure. Do not allow packaging chips to enter the unit.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...