9-20
AC10 Inverter
F312 At Speed threshold
Setting range: 0.00
~
5.00Hz
Mfr’s value: 0.00
When F300=15 or F301=15, threshold range is set by F312.
For example: when F301=15, target frequency is 20HZ and F312=2, the running frequency
reaches 18Hz (20-2), ON signal is output by DO1 until the running frequency reaches target
frequency.
9.3.2 Digital multifunctional input terminals
F316 DI1 terminal function setting
Setting range:
0: no function
1: Run
2: Stop
3: Multi-stage speed terminal 1
4: Multi-stage speed terminal 2
5: Multi-stage speed terminal 3
6: Multi-stage speed terminal 4
7: Reset
8: Free stop
9: External coast stop
10: Acceleration/deceleration forbidden
11: Forward run jogging
12: Reverse run jogging
13: UP frequency increasing terminal
14: DOWN frequency decreasing terminal
15: “FWD” terminal
16: “REV” terminal
17: Three-line type input “X” terminal
18: Acceleration/deceleration 1
19: Reserved
20: Speed/torque switchover
21: Frequency source switchover
32: Fire control switchover
33: Emergency fire control
34: Accel / decel switchover 2
37: Common-open PTC heat protection
38: Common-close PTC heat protection
48: High-frequency switchover
52: Jogging (no direction)
53: Watchdog
54: Frequency reset
55: switchover between manual running and
auto running
56: Manual running
57: Auto running
58: Direction
Mfr’s value: 11
F317 DI2 terminal function setting
Mfr’s value: 9
F318 DI3 terminal function setting
Mfr’s value: 15
F319 DI4 terminal function setting
Mfr’s value: 16
F320 DI5 terminal function setting
Mfr’s value: 7
F321 DI6 terminal function setting
Mfr’s value: 8
F322 DI7 terminal function setting
Mfr’s value: 0
F323 DI8 terminal function setting
Mfr’s value: 0
This parameter is used for setting the corresponding function for multifunctional digital input
terminal.
Both free stop and external coast stop of the terminal have the highest priority.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...