AC10 Inverter
F303 DO1 output types selection
Setting range:
0: level output
1 : pulse output
Mfr’s value: 0
When level output is selected, all terminal functions in table 9-2 can be defined by F301.
When pulse output is selected, DO1 can be defined as high-speed pulse output terminal. The
max pulse frequency is 50KHz. The related function codes are F449
、
F450
、
F451
、
F452
、
F453.
F307 Target frequency 1
Setting range: F112
~
F111Hz
Mfr’s value: 10.00Hz
F308 Target frequency 2
Mfr’s value: 50.00Hz
F309 Frequency width
Setting range: 0
~
100
%
Mfr’s value: 50
When F300, F301, or F302 = 2 or 3 and
characteristic frequency (F307) is
selected, this group function codes set
characteristic frequency and its width.
For example:
F301 (DO1 assignment) =2,
F307 (Target Frequency 1) =10,
F309 (Target frequency width) =10,
When frequency is higher than F307,
DO1 becomes true until the frequency is
lower than (10-10*10%
)
= 9Hz, then
DO1 becomes false.
F310 Target current
Setting range: 0
~
5000
Mfr’s value: Rated
current
F311 Target current width
Setting range: 0
~
100
Mfr’s value: 10
When F300 or F301=17 (Over latent
current) is selected, this group function
codes set characteristic current and its
width.
For example:
F301 (DO1 assignment) =17,
F310 (Target Current) =100,
F311 (Current width) =10,
When inverter current is higher than F310,
DO1 becomes true until inverter current is
lower than
(
100-100*10%
)
= 90A, then
DO1 becomes false.
D01=0
D01=1
F307 (Hz) – 100*(F309) = W
10Hz
F307
(%)
F309 %
9Hz
W
D01=0
D01=1
F310 (A) – 100*(F311) = W
100A
F310
(%)
F311 %
90A
W
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...