6-3
AC10 Inverter
6.1.2 Panel Display
Table 6-4 Items and Remarks Displayed on the Panel
Items
Remarks
AErr
Analog Input has open connection
CE
Indicates Communication error
Err2
Tuning parameters are set wrong
Err3
Instantaneous Over Current
Err4
Current Sampling Fault
Err5
PID parameters are set wrong
Err6
Watchdog Fault
ESP
External coast stop terminal is closed, ESP will be displayed.
FL
Indicates Flycatching fault condition
LU
Indicates under-voltage for input condition
HF-0
This Item will be displayed when you press “M” in stopping status, which
indicates jogging operation is valid. But HF-0 will be displayed only after
you change the value of F132.
-HF-
It stands for resetting process and will display target frequency after reset.
OC
Indicates over-current condition (OC)
OC1
Indicates over-current condition (OC1)
OE
Indicates over-voltage condition
OH
Indicates heatsink over-heat condition
OH1
Indicates external over-heat condition
OL1
Indicates inverter over-load condition
OL2
Indicates motor over-load condition
PF0
Indicates phase loss for output condition
PF1
Indicates phase loss for input condition
10.00
Indicating inverter’s current running frequency (or rotate speed) and
parameter setting values, etc.
Flashing in stopping status to display target frequency.
0.
Holding time when changing the running direction. When “Stop” or “Free
Stop (Coast Stop)” command is executed, the holding time can be
cancelled.
A100
Output current (100A). Keep one digit to the right of the decimal point
when current is below 100A.
b*.*
PID feedback value is displayed.
F152
Function code (parameter code).
H *
Heat Sink temperature is displayed.
L***
Linear speed is displayed.
o*.*
PID given value is displayed.
u100
DC Bus voltage (100V).
U100
Output voltage (100V).
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...