9-16
AC10 Inverter
F216 Auto-start restart attempts
Setting range:
0
~
5
Mfr’s value: 0
F217 Fault reset delay
Setting range:
0.0
~
10.0
Mfr’s value:
3.0
F216 sets the most times of auto-starting in case of repeated faults. If starting times are more
than the setting value of this function code, inverter will not reset or start automatically after
fault. Inverter will run after running command is given to inverter manually.
F217 sets delay time for fault reset. The range is from 0.0 to 10.0s which is time interval from
fault to resetting.
F219 Write EEPROM by Modbus
Setting range:
0: Disable
1: Enable
Mfr’s value: 1
F220 Frequency memory after power-down
Setting range:
0: Disable
1: Enable
Mfr’s value: 0
F220 sets whether or not frequency remember after power-down is valid.
This function is valid for F213 and F214. Whether or not to memory running state after power-
down or malfunction is set by this function.
The function of frequency memory after power-down is valid for main frequency and secondary
frequency that is given by digital. Because the digital given secondary frequency has positive
polarity and negative polarity, it is saved in the function codes F155 and F156.
Table 9-1 Combination of Speed Control
F204
F203
0. Memory of
digital setting
1 External
analog AI1
2 External
analog AI2
4 Terminal stage
speed control
5 PID
adjusting
0 Memory of
digital setting
〇
●
●
●
●
1 External analog AI1
●
〇
●
●
●
2 External analog AI2
●
●
〇
●
●
4 Terminal Stage
speed control
●
●
●
〇
●
5 Digital setting
〇
●
●
●
●
9 PID adjusting
●
●
●
●
〇
10 MODBUS
●
●
●
●
●
●: Inter-combination is allowable.
〇
: Combination is not allowable.
The mode of automatic cycle speed control is unable to combine with other modes. If the
combination includes the mode of automatic cycle speed control, only main speed control
mode will be valid.
F224=1, when target frequency is lower than Min frequency, inverter will run at Min frequency.
F224 when target frequency is lower than
Min frequency
Setting range:
0: stop
1: run at min frequency
Mfr’s value: 1
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...