9-22
AC10 Inverter
Value Function
Instructions
When this input is true, and F207=3, the main
frequency source is switched with the sum of the main
and the secondary frequency sources.
32
Fire pressure switchover
When PID control is valid and this terminal is valid, the
setting value of PID switches into fire pressure given
(FA58).
33
Emergency fire control
When emergency fire mode (FA59) is valid, inverter
will be in emergency fire mode.
34
Acceleration / deceleration
switchover 2
Please refer to Table 9-4.
37
Normally-open PTC heat
protection
A normally-open contact is connected to monitor
motor temperature. When this input is true, and the
inverter is in the running status, the inverter will trip
into OH1.
38
Normally-closed PTC heat
protection
A normally-closed contact is connected to monitor
motor temperature. When this input is false, and the
inverter is in the running status, the inverter will trip
into OH1.
48
High-frequency switchover
When this function is valid, inverter will switch into
high-frequency optimizing mode.
52
Jogging (no direction)
In the application 1 and 2, the direction of jogging
command is controlled by terminal set to 58:
direction.
53
Watchdog
During the time set by F326 elapses without an
impulse being registered, inverter will trip into Err6,
and inverter will stop according to stop mode set by
F327.
54
Frequency reset
In the application 4, if the function is valid, target
frequency will change to the value set by F113.
55
Switchover between manual
run and auto run
In application 2, when this input is true, the inverter
can be switched between manual and auto run
using terminals set to 55 and 56.
56
Manual run
In the application 2, if the function is valid, inverter
will run manually.
57
Auto running
In the application 2, if the function is valid, inverter
will run automatically.
58
Direction
Run / Jog direction. When this input is true, the
inverter will run/jog reverse. When this input is
false, the inverter will run/jog forward.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...