AC10 Inverter
Figure 9-6 PTC Heat Protection
When the coding switch is in the end of “NPN”, PTC resistor should be connected between CM
and DIx terminal. When the coding switch is in the end of “PNP”, PTC resistor should be
connected between DIx and 24V. The recommended resistor value is 16.5KΩ.
Because the accuracy of external PTC has some differences with manufacture variation some
errors can exist, thermistor protection relay is recommended.
NOTE: To use this function double insulate motor thermistor must be used.
Table 9-4 Accel/decel selection
Accel/decel
switchover 2 (34)
Accel/decel
switchover 1 (18)
Present accel/decel time
Related
parameters
0
0
The first accel/decel time
F114, F115
0
1
The second accel/decel time
F116, F117
1
0
The third accel/decel time
F277, F278
1
1
The fourth accel/decel time
F279, F280
Table 9-5 Instructions for multistage speed
K4 K3
K2
K1
Frequency setting
Parameters
0
0
0
0
Multi-stage speed 1
F504/F519/F534/F549/F557/F565
0
0
0
1
Multi-stage speed 2
F505/F520/F535/F550/F558/F566
0
0
1
0
Multi-stage speed 3
F506/F521/F536/F551/F559/F567
0
0
1
1
Multi-stage speed 4
F507/F522/F537/F552/F560/F568
0
1
0
0
Multi-stage speed 5
F508/F523/F538/F553/F561/F569
0
1
0
1
Multi-stage speed 6
F509/F524/F539/F554/F562/F570
0
1
1
0
Multi-stage speed 7
F510/F525/F540/F555/F563/F571
0
1
1
1
Multi-stage speed 8
F511/F526/F541/F556/F564/F572
1
0
0
0
Multi-stage speed 9
F512/F527/F542/F573
1
0
0
1
Multi-stage speed 10 F513/F528/F543/F574
1
0
1
0
Multi-stage speed 11 F514/F529/F544/F575
1
0
1
1
Multi-stage speed 12 F515/F530/F545/F576
1
1
0
0
Multi-stage speed 13 F516/F531/F546/F577
1
1
0
1
Multi-stage speed 14 F517/F532/F547/F578
1
1
1
0
Multi-stage speed 15 F518/F533/F548/F579
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...