AC10 Inverter
F127/F129 Skip Frequency A,B (Hz)
Setting range:
0.00
~
590.0
Mfr’s value:0.00Hz
F128/F130 Skip Width A,B (Hz)
Setting range:
±2.5
Mfr’s value: 0.0
Systematic vibration may occur when the motor is running at a certain frequency. This
parameter is set to skip this frequency.
The inverter will skip the point automatically when output frequency is equal to the set value of
this parameter.
“Skip Width” is the span from the upper to the lower limits around Skip Frequency. For
example, Skip Frequency=20Hz, Skip Width=±0.5Hz, inverter will skip automatically when
output is between 19.5
~
20.5Hz.
The inverter will not skip this frequency span during acceleration/deceleration.
Note: During the
process of
Flycatching, skip
frequency function is
invalid. After
Flycatching is
finished, this function
is valid.
Figure 9-2 Skip Frequency
F131 Running
Display Items
0
-
Current output frequency/function-code
1
-
Output rotary speed
2
-
Output current
4
-
Output voltage
8
-
DC Bus Voltage
16
-
PID feedback value
32
-
Temperature
64
-
Reserved
128
-
Linear speed
256
-
PID given value
512
-
Reserved
1024
-
Reserved
2048
-
Output power
4096
-
Output torque
Mfr’s value:
0+1
+
2
+
4
+
8=15
Selection of one value from 1, 2, 4, 8, 16, 32, 64 and 128 shows that only one specific display
item is selected. Should multiple display items be intended, add the values of the
corresponding display items and take the total values as the set value of F131, e.g., just set
F131 to be 19 (1+2+16) if you want to call “current output rotary speed”, “output current” and
“PID feedback value”. The other display items will be covered.
As F131
=
8191, all display items are visible, of which, “frequency/function-code” will be visible
whether or not it is selected.
Should you intend to check any display item, press the “M” key for switchover.
Refer to the following table for each specific value unit and its indication:
Time (t)
Output Frequency
(
Hz
)
F128
F130
F129
F127
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...