7.4 Functions of Control Terminals
To operate the inverter the user must operate the control terminals correctly and flexibly. The
following is a description of the user terminals and any relevant parameters.
Table 7-3 Functions of Control Terminals
Terminal
Type
Description
Function
DO1
Output Signal
Multifunctional
output terminal 1 When the function is true, the value between
this terminal and CM is 0V; when the function
is false, the value is 24V. Output current
2mA.
The functions of output
terminals shall be defined
per manufacturer’s value.
Their initial state may be
changed through changing
function codes.
DO2
Note 1
Multifunctional
output terminal 2
TA
TB
TC
Relay contact
TC is a common point, TB-TC are normally
closed contacts, TA-TC are normally open
contacts. The contact capacity is 10A/125VAC,
5A/250VAC, 5A/30VDC.
(See note 3)
AO1
Analog output
Running
frequency
It is connected with frequency meter, speedometer or ammeter externally,
and its minus pole is connected with GND. See F423
~
F426 for details.
AO2
Current display
10V
Analog power
supply
Self contained
power supply
Internal 10V self-contained power supply of the inverter provides power to
the inverter. When used externally, it can only be used as the power
supply for voltage control signal, with current restricted below 20mA.
AI1
Input Signal
Voltage / Current
analog input
When analog speed control is selected, the voltage or current signal is
input through this terminal. The range of voltage input is 0~10V and the
current input is 0
~
20mA, the input resistor is 500Ohm, and grounding:
GND. If the input is 4
~
20mA, it can be realised by setting F406 to 2. The
voltage or current signal can be chosen by coding switch. See
for details, the default setting of AI1 is 0~10V, and the
default setting of AI2 is 0-20mA.
AI2
GND
Self-contained
Power
supply Ground
Ground terminal of external control signal (voltage control signal or current
source control signal) is also the ground of 10V power supply of this
inverter.
24V
Power
supply
Control power
supply
Power: 24±1.5V, grounding is CM; current is restricted below 50mA for
external use.
DI1
Digital input
control terminal
Jogging terminal
When this terminal is valid, the inverter
will have jogging running. The jogging
function of this terminal is valid under
both at stopped and running status.
The functions of input terminals
shall be defined per
manufacturer’s value. Other
functions can also be defined by
changing function codes.
Note 4
DI2
External
Coast Stop
When this terminal is valid, “ESP”
malfunction signal will be displayed.
DI3
“FWD” Terminal
When this terminal is valid, inverter will
run forward.
DI4
“REV” Terminal
When this terminal is valid, inverter will
run reverse.
DI5
Reset terminal
Make this terminal valid under fault
status to reset the inverter.
DI6
Note 1
Free stop
Make this terminal valid during running
can realize free stop.
DI7
Note 1
Run Terminal
When this terminal is in the valid state,
inverter will run by the acceleration
time.
DI8
Note 1
Stop terminal
Make this terminal valid during running
can realize stop by the deceleration
time.
GND
Note 2
RS485
communication
terminals
Grounding of
differential signal Ground of differential signal
5V
Note 2
Power of
differential signal Power of differential signal
A+
Note 2
Positive polarity
of differential
signal
Standard: TIA/EIA-485(RS-485)
Communication protocol: Modbus
Communication rate: 1200/2400/4800/9600/19200/38400/57600bps
B-
Note 2
Negative polarity of
Differential signal
Note 1: This terminal is not included in 22kW and below 22Kw inverters.
Note 2: GND, 5V, A+, and B- are on separate 4-pole terminal block.
Note 3: The contact capacity for 30kW and above 30kW inverters is 10A/125VAC, NO/NC 3A, 250VAC/30VDC.
Note 4: The “true” state for these terminals is either 24V when configured for PNP operation or 0V when configured for NPN
Operation.
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...