9-42
AC10 Inverter
F812 Pre-exciting time
Setting range: 0.000
~
30.00s
0.30s
F813 Rotary speed loop KP1
Setting range:
0.01
~
20.00 (for 22kW and below
22kW)
1~100 (for above 22kW)
Subject to inverter
model
F814 Rotary speed loop KI1
Setting range:
0.01
~
2.00 (for 22kW and below
22kW)
0.01~10.00 (for above 22kW)
Subject to inverter
model
F815 Rotary speed loop KP2
Setting range:
0.01
~
20.00 (for 22kW and below
22kW)
1~100 (for above 22kW)
Subject to inverter
model
F816 Rotary speed loop KI2
Setting range:
0.01
~
2.00 (for 22kW and below
22kW)
0.01~10.00 (for above 22kW)
Subject to inverter
model
F817 PID switching frequency 1 Setting range: 0~F111
5.00
F818 PID switching frequency 2 Setting range: F817~F111
50.00
Figure 9-14 PID parameter
Dynamic response of vector control speed can be adjusted through adjusting gains of speed
loop. Increasing KP and KI can speed up dynamic response of speed loop. However, if
proportional gain or integral gain is too large, it may give rise to oscillation.
Recommended adjusting procedures:
Make fine adjustment of the value starting from the manufacturer value if the manufacturer
setting value cannot meet the needs of practical application. Be cautious that amplitude of
f
KP
F815
F813
F817
F818
F818
F817
F816
F814
f
KI
F801=3.7
F802=
380
F803=8.8 F805=
1440
F810=
50
F800=1
Press
“
I
”
key
TEST is
displayed
Target
frequency is
blinking
Ok
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...