Parameter Reference
15-11
AC10 Inverter
Multi-stage Speed Control: F500-F580
Function
Code
Function
Definition
Setting Range
Mfr’s Value Change
F500
Stage speed type
0: 3-stage speed;
1: 15-stage speed;
2: Max 8-stage speed auto circulating
1
╳
F501
Selection of Stage Speed Under Auto-
circulation Speed Control
2
~
8
7
√
F502
Selection of Times of Auto- Circulation
Speed Control
0
~
9999
(
when the value is set to 0, the
inverter will carry out infinite circulating
)
0
√
F503
Status after auto circulation running
Finished
0: Stop
1: Keep running at last stage speed
0
√
F504
Frequency setting for stage 1 speed
F112
~
F111
5.00Hz
√
F505
Frequency setting for stage 2 speed
F112
~
F111
10.00Hz
√
F506
Frequency setting for stage 3 speed
F112
~
F111
15.00Hz
√
F507
Frequency setting for stage 4 speed
F112
~
F111
20.00Hz
√
F508
Frequency setting for stage 5 speed
F112
~
F111
25.00Hz
√
F509
Frequency setting for stage 6 speed
F112
~
F111
30.00Hz
√
F510
Frequency setting for stage 7 speed
F112
~
F111
35.00Hz
√
F511
Frequency setting for stage 8 speed
F112
~
F111
40.00Hz
√
F512
Frequency setting for stage 9 speed
F112
~
F111
5.00Hz
√
F513
Frequency setting for stage 10 speed
F112
~
F111
10.00Hz
√
F514
Frequency setting for stage 11 speed
F112
~
F111
15.00Hz
√
F515
Frequency setting for stage 12 speed
F112
~
F111
20.00Hz
√
F516
Frequency setting for stage 13 speed
F112
~
F111
25.00Hz
√
F517
Frequency setting for stage 14 speed
F112
~
F111
30.00Hz
√
F518
Frequency setting for stage 15 speed
F112
~
F111
35.00Hz
√
F519-
F533
Acceleration time setting for the speeds from
Stage 1 to stage 15
0.1
~
3000S
Subject to
inverter
model
√
F534-
F548
Deceleration time setting for the speeds from
Stage 1 to stage 15
0.1
~
3000S
√
F549-
F556
Running directions of stage speeds from
Stage 1 to stage 8
0: Forward running;
1: Reverse running
0
√
F557-
F564
Running time of stage speeds from Stage
1 to stage 8
0.1
~
3000S
1.0S
√
F565-
F572
Stop time after finishing stages from Stage
1 to stage 8.
0.0
~
3000S
0.0S
√
F573-
F579
Running directions of stage speeds from
Stage 9 to stage 15.
0: Forward running;
1: Reverse running
0
√
F580
Reserved
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...