AC10 Inverter
When F106 (Control Mode) = 2, the function of F137 is enabled.
To compensate low-frequency torque controlled
by V/HZ, output voltage of inverter while low-
frequency should be compensated.
When F137=0, linear compensation is chosen
and it is applied on universal constant-torque
load;
When F137=1, square compensation is chosen
and it is applied on the loads of fan or water
pump;
When F137=2, user-defined multipoint
compensation is chosen and it is applied on the
special loads of spin-drier or centrifuge;
Figure 9-3 Torque Promotion
This parameter should be increased when the load is heavier, and this parameter should be
decreased when the load is lighter.
If the torque is elevated too much, the motor overheats easily, and the current of inverter will
be too high. Please check the motor while elevating the torque.
When F137=3, auto torque compensation is chosen and it can compensate low-frequency
torque automatically, to diminish motor slip, to make rotor rotary speed close to synchro rotary
speed and to restrain motor vibration. Customers should correctly set motor power, rotary
speed, numbers of motor poles, motor rated current and stator resistance. Please refer to the
chapter “Operation process of measuring motor parameters”.
F140 Voltage compensation point
frequency (Hz)
Setting range: 0
~
F142
Mfr’s value:
1.00
F141 Voltage compensation point 1 (%) Setting range: 0
~
100
%
Subject to
inverter model
F142 User-defined frequency point F2
Setting range: F140
~
F144
Mfr’s value:
5.00
F143 User-defined voltage point V2
Setting range: 0
~
100
%
Mfr’s value: 13
F144 User-defined frequency point F3
Setting range: F142
~
F146
Mfr’s value:
10.00
F145 User-defined voltage point V3
Setting range: 0
~
100
%
Mfr’s value: 24
F146 User-defined frequency point F4
Setting range: F144
~
F148
Mfr’s value:
20.00
F147 User-defined voltage point V4
Setting range: 0
~
100
%
Mfr’s value: 45
F148 User-defined frequency point F5
Setting range: F146
~
F150
Mfr’s value:
30.00
F149 User-defined voltage point V5
Setting range: 0
~
100
%
Mfr’s value: 63
F150 User-defined frequency point F6
Setting range: F148
~
F118
Mfr’s value:
40.00
F151 User-defined voltage point V6
Setting range: 0
~
100
%
Mfr’s value: 81
Multi-stage V/HZ curves are defined by 12 parameters from F140 to F151.
20
f
Turnover
frequency
V
(%)
1
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...