Parameter Reference
15-15
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value Change
F732
Voltage Threshold of Under-voltage
Protection
0~450
Subject to
inverter
model
○
F737
Over-current 1 Protection
0: Disabled
1: Enabled
0
F738
Over-current 1 Protection Coefficient
0.50
~
3.00
2.50
F739
Over-current 1 Protection Record
△
F740
Reserved
F741
Analog Disconnected Protection
0: Disabled
1: Stop and AErr displays.
2: Stop and AErr is not displayed.
3: Inverter runs at the min frequency.
4: Reserved.
0
√
F742
Threshold of Analog Disconnected
Protection (%)
1~100
50
○
F745
Threshold of Pre-alarm Overheat (%)
0~100
80
○
*
F747
Carrier Frequency Auto-adjusting
0: Disabled
1: Enabled
1
√
F754
Zero-current Threshold (%)
0~200
5
╳
F755
Duration time of zero-current
0~60
0.5
√
Motor parameters: F800-F830
Function
Code
Function
Definition
Setting Range
Mfr’s Value Change
F800
Motor’s Parameters Selection
Setting range:
0: Disabled;
1: Rotating tuning.;
2: Stationary tuning
0
╳
F801
Rated Power
0.2
~
1000kW
○╳
F802
Rated Voltage
1
~
440V
○╳
F803
Rated Current
0.1
~
6500A
○╳
F804
Number of Motor Poles
2
~
100
4
○△
F805
Rated Rotary Speed
1
~
30000
○╳
F806
Stator Resistance Ω
0.001
~
65.53Ω (22kW and below)
0.1~6553mΩ (above 22kW)
Subject to
inverter
model
○╳
F807
Rotor Resistance Ω
0.001
~
65.53
Ω
(22kW and below)
0.1~6553mΩ (above 22kW)
Subject to
inverter
model
○╳
F808
Leakage Inductance(mH)
0.01
~
655.3mH (22kW and below)
0.001~65.53mH (above 22kW)
Subject to
inverter
model
○╳
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...