9-26
AC10 Inverter
For example: when F400=1, F402=8, if analog input voltage is lower than 1V, system judges it
as 0. If input voltage is higher than 8V, system judges it as 10V (suppose analog channel
selects 0-10V). If Max frequency F111 is set to 50Hz, the output frequency corresponding to 1-
8V is 0-50Hz.
The filtering time constant is set by F405.
The greater the filtering time constant is, the more stable for the analog testing. However, the
precision may decrease to a certain extent. It may require appropriate adjustment according to
actual application.
Channel proportional gain is set by F404.
If 1V corresponds to 10Hz and F404=2, then 1V will correspond to 20Hz.
Corresponding setting for upper / lower limit of analog input are set by F401 and F403.
If Max frequency F111 is 50Hz, analog input voltage 0-10V can correspond to output frequency
from -50Hz
to
50Hz by setting these group function codes. Please set F401=0 and F403=2,
then 0V corresponds to -50Hz, 5V corresponds to 0Hz and 10V corresponds to 50Hz. The unit
scaling the upper / lower limit of input is in percentage (%). If the value is greater than 1.00, it
is positive; if the value is less than 1.00, it is negative. (e.g. F401=0.5 represents –50%).
If the running direction is set to forward running by F202, then 0-5V corresponding to the
minus frequency will cause reverse running, or vice versa.
Figure 9-8 Correspondence of analog input to setting
The unit of for scaling the upper / lower
limit of input is in percentage (%). If the
value is greater than 1.00, it is positive; if
the value is less than 1.00, it is negative.
(e.g. F401=0.5 represents –50%).
The corresponding setting benchmark: in
the mode of combined speed control,
analog is the secondary frequency and
the setting benchmark for range of
secondary frequency which relatives to
main frequency is “main frequency X”;
corresponding setting benchmark for other cases is the “max frequency”, as illustrated in the
above figure.
AI1
AI2
A
(F401-1)
(F407-1)
Should be max frequency (F111)
B
(F403-1)
(F409-1)
Should be max frequency (F111)
C
F400
F406
Low limit of Aix channel input (V)
D
F402
F408
Upper limit of Aix channel input (V)
AI1
B
A
D
C
F409 = 2
100%
F407 = 1
0%
10V
(20mA)
Voltage (V)
Corresponding Frequency (Hz)
0V
(0mA)
AI
F409 = 2
100%
10V
(20mA)
Voltage (V)
Corresponding Frequency (Hz)
F407 = 1
-100%
0V
(0mA)
0%
AI
Summary of Contents for 10G-46-0600-BF
Page 2: ......
Page 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Page 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Page 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Page 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Page 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Page 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Page 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...