PA-7000 Series Firewall Module and Interface Card Information
LED
Description
QSFP LEDs
These LEDs indicate link and activity. The color of the LED
indicates the port speed.
•
Green
—The port is operating at 10Gbps
•
Yellow
—The port is operating at 40Gbps
To learn about the orientation of the LED indicators, see
.
PA-7000 Series Firewall LFC Requirements
The following information describes the system and hardware requirements for upgrading to the
Log Forwarding Card (LFC).
If you install the Switch Management Card (SMC-B), Log Forwarding Card (LFC), or
PA-7000 100G NPC in a PA-7050 firewall, you must install the second-generation fan
trays (PA-7050-FANTRAY-L-A and PA-7050-FANTRAY-R-A). If you install these cards
in a PA-7080 firewall, you must also install the electromagnetic interference (EMI) filter.
You do not have to install these components if the last five digits of the firewall serial
number is 10,000 or greater because the PA-7050 will have the second-generation fan
trays installed and the PA-7080 will have a built-in EMI filter.
• PAN-OS 9.0 or later.
• Remove the Log Processing Card (LPC) before you install the Log Forwarding Card (LFC).
• (
PA-7050 only
) Install the second-generation fan tray to increase cooling capacity. The
topic shows how to install a fan tray.
• Replace the first-generation SMC (PA-7050-SMC or PA-7080-SMC) with the
SMC (PA-7050-SMC-B or PA-7080-SMC-B).
The LFC is only compatible with the SMC-B.
Install the PA-7080 Firewall EMI Filter
to reduce electromagnetic interference.
PA-7000 Series Firewall Hardware Reference
53
©
2023 Palo Alto Networks, Inc.