PA-7000 Series Firewall Installation
STEP 6 |
Connect the two-post lug connector to the two-post lugs on the chassis using the provided
star washers and nuts and then torque the nuts to 50 in-lbs. You can install the lug in a
vertical or horizontal position. Be careful not to strip the threads on the nuts and lug studs.
STEP 7 |
Connect the first two power supplies (PEM A power inlets 1 and 2) to the appropriate
(120VAC 15#amp circuit breaker or 240VAC 20-amp) circuit breaker using the provided
power cords and then connect the second two power supplies (PEM B power inlets 1 and 2)
to a second appropriate and independent (120VAC 15#amp circuit breaker or 240VAC 20-
amp) circuit breaker.
If you connect 120VAC power and you install five or six NPCs in a PA-7050 firewall
or ten NPCs in a PA-7080 firewall, you can configure only partial redundancy. Full
redundancy is not possible because the chassis do not hold twice the minimum number
of active 120VAC power supplies required to power the chassis and the NPCs.
STEP 8 |
Secure the power cords to the power inlets using the power cord retainer clips.