DETAILED SETTINGS
8.
Use the LEFT and RIGHT Keys to display
FOCUS on the main display.
Selecting Current (mA) or Voltage (V) Output
9.
Press the UP or DOWN Key.
The sub-display will flash.
10.
Display mA.
Always select the same output as the current/voltage switch selection on the bottom of the Amplifier
Unit.
Setting the First Point (A)
11.
Press the ENT Key.
The display will change to allow the first-point settings to
be made. The output current value will be displayed on
the main display, and the corresponding measured value
will be displayed on the sub-display and the leftmost digit
will flash.
12.
Set the output current value and the corre-
sponding measured value for the first point.
Set a measured value within the measurement distance.
If scaling or calculation has been set, set a value that
reflects those settings.
The flashing digit, i.e., the digit for which a value can be set, will change as shown in the diagram.
Move between digits.
Increment and decre-
ment the numeric value.
Sub-display
digit movement
Digit moves
one at a
time
Movement between main display
and sub-display (from leftmost or
rightmost digit of sub-display)
Z166-E1-02A.book Page 105 Friday, June 3, 2005 4:18 PM
Summary of Contents for ZX-E -
Page 4: ...2 Preface ZX E Operation Manual Preface ...
Page 8: ...6 Preface Contents ZX E Operation Manual Preface ...
Page 11: ...9 ZX E Operation Manual Preface PREFACE ...
Page 12: ...10 Preface ZX E Operation Manual PREFACE ...
Page 17: ...Section 1 FEATURES 15 ZX E Operation Manual Section 1 FEATURES ZX E Features 16 ...
Page 24: ...22 Section 1 ZX E Features ZX E Operation Manual Section 1 FEATURES ...
Page 62: ...60 Section 3 Adjusting Linearity ZX E Operation Manual Section 3 BASIC OPERATION ...
Page 162: ...160 Appendices Quick Reference for Displays ZX E Operation Manual APPENDICES ...