36
2-4-3 Wiring the Power Supply
Use a power supply that meets the following specifications.
CHECK
Use a DC power supply with countermeasures against high-voltage spikes (safe
extra low-voltage circuits on the secondary side).Excessively high voltages can
result in electric shock.
Notice
- Wire the Power Supply Unit independently of other devices. In particular,
keep the power supply wired separately from inductive loads.
- Keep the power supply wiring as short as possible. (10 m max.)
- If UL recognition is required, use a UL class II power supply.
Recommended Power Supply: OMRON S82K-05024
Output current
1.6 A min.
Power supply voltage
24 VDC (21.6 to 26.4VDC)
+
-
24VDC
Power Supply and Ground
Section 2-4