Status Information and Troubleshooting
Section 9-2
BYTE
byStatus1
Reserved area
Stores undetermined data.
BYTE
byStatus2
BYTE
byStatus3
BYTE
byStatus4
Reserved area
Stores undetermined data.
BYTE
byStatus5
BYTE
byStatus6
Reserved area
Stores undetermined data.
Type
Variable name
Contents
Baud rate, power supply status, terminating resistance setting status
For Wired Systems, stores the set baud rate and the setting of the
terminating resistance switch.
For Optical Ring System, stores the power supply status.
Bit
Baud rate
0x1: 2 Mbits/s
0x2: 1 Mbits/s
0x3: 500 kbits/s
Wired System
0: Terminating resistance switch OFF
1: Terminating resistance switch O
N
Optical System
0:
N
o backup power supply
1: Backup power supply
Error information 1
Stores information such as whether or not there is an error log recorded,
node address setting errors, etc.
1: Error history
1: Fatal data link error
1: Communications controller send
section error
1:
N
ode address setting error
1:
N
ode address duplicated
1:
N
etwork parameter mismatch
1: Communications controller
hardware error
Error information 2
Stores information such as EEPROM write errors, setting table errors, etc.
1: EEPROM write error
Bit
1:
N
etwork parameter error
1: Data link table error
1: Routing table error
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......