83
Starting and Stopping Data Links
Section 5-3
5-3-1
Using a Programming Device or a Ladder Program
Set the software switches (AR or DM Start Bit) in the PC to ON using a Pro-
gramming Device or from the ladder-diagram program.
The data links will start when the Start Bit changes from OFF to ON or is
already ON when power is turned ON. The data links will stop when the Start
Bit changes from ON to OFF.
Note
1. Refer to the
Controller Link Units Operation Manual
(W309 or W370) for
details on starting and stopping data links using a Programming Device or
ladder program.
2. The data in the AR and DM Areas is retained when power is turned off.
Therefore, by setting in the AR and DM Areas can be made in advance to
start data links as soon as power is turned on. It is recommended to set the
Start Bit to ON in multiple nodes that are participating in the data link so
that the data links will start even if the startup node is down. The same data
link settings must be set in these nodes for automatically set data links.
CS-series or CJ-series Startup Node
C200HX/HG/HE Startup Node
Programming De
v
ice
User program
Startup node
Controller Link
CS/CJ-series PCs
Turn O
N
the Start Bit in DM 3000 + 100
×
N
.
(
N
: unit number)
C200HX/HG/HE PCs
Turn O
N
the Start Bit in AR 07
CV-series PCs
Turn O
N
the Start Bit in DM 2000 + 100
×
N
.
(
N
: unit number)
+
Data link Start Bit
Start: Changed from OFF to O
N
or set to O
N
when power is turned on
Stop: Changed from O
N
to OFF
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Word
N
N
: DM 30000 + 100
×
(unit number)
Data link Start Bit for le
v
el 0 (AR 0700)
Start: Changed from OFF to O
N
or set to O
N
when power is turned on
Stop: Changed from O
N
to OFF
Data link Start Bit of le
v
el 1 (AR 0704)
Start: Changed from OFF to O
N
or set to O
N
when power is turned on
Stop: Changed from O
N
to OFF
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
AR 07
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......