98
Commands and Responses for the Support Board
Section 6-3
Status 2 (response):
This byte contains the following information for Control-
ler Link Support Boards. (It is always 00 Hex for Wired Controller Link Support
Boards.)
Status 3 (response):
Error information. The configuration is as follows:
Note
A network parameter error occurs if the registered network parameter con-
tents do not match the actual network parameter contents after the power is
turned on. The system, however, will not stop. When a network parameter
error occurs, the actual network parameter contents are automatically regis-
tered to that Unit.
Status 5 (response):
Error information related to the Support Board and the
PC. The configuration is as follows:
A network parameter error, data link table error, or routing table error occurs if
an error is discovered when the parameters and tables are checked at power
up.
A PC system setting error occurs if the Controller Link Unit is not properly rec-
ognized by a CS-series, CJ-series, or CV-series PC.
A PC model error occurs if a C200HX/HG/HE Controller Link Unit is mounted
to another type of PC.
Count 1 to Count 8 (response):
The total number of times for each of the
items listed below is returned as 1 byte of hexadecimal data.
Count 1:
Number of CRC errors
Count 2:
Number of token re-sends
Count 3:
Number of token returns
Count 4:
Number of token timeouts
Count 5:
Number of polling timeouts
Count 6:
Number of controller changes
Count 7:
Number of active node changes
Count 8:
Reserved for system use.
Bit
Baud rate setting
0001: 2 Mbps
0010: 1 Mbps
0011: 500 Kbps
7
6
5
4
3
2
1
0
0 0 0
Wired System
0: Terminating resistance switch OFF
1: Terminating resistance switch O
N
Optical System
0:
N
o backup power supply
1: Backup power supply
1: Error log exists
1: Data link error stop
1: Controller transmitter error
1:
N
ode address setting error
1: Duplicate node address setting error
1:
N
etwork parameter error
1: Controller hardware error
7
0
6
5
4
3
2
1
0
Bit
1: EEPROM error
1: PC model error
(C200HX/HG/HE only)
1: PC system setting error
(CV-series PCs only)
1:
N
etwork parameter error
1: Data link table error
1: Routing table error
7
0
6
5
4
3
2
1
0
0
Bit
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......