FINS Command/Response Format
Section 6-2
6-2
FINS Command/Response Format
This section explains the format of the FINS commands and responses spec-
ified by the “
clksend
” library function.
When actually sending or receiving message service data, the contents spec-
ified by the library function parameters are attached as a header. When the
message service is used, however, there is normally no need to pay special
attention to headers.
6-2-1
Headers
Although parameters are used to designate the source, the destination, and
other required information, there are some cases where a header must be
manually added before the command code. Refer to the operation manuals
for individual systems to determine if a header is required. The header format
described below is attached before the command code and the other parame-
ters described for individual commands in the rest of this manual.
Command Data Structure
Response Data Structure
Details
ICF
Information control field. Individual bits of the ICF are used as follows:
Note
All settings below are shown in hexadecimal except where otherwise indi-
cated.
RSV
Reserved. Set to 00.
GCT
Gateway count. Set to 02.
DNA
Destination network address. Specify within the following ranges.
00:
Local network
01 to 7F: Remote network (1 to 127 decimal)
DA1
Destination node number. Specify within the following ranges.
01 to 3E:
Node number in Controller Link network (1 to 62 decimal)
01 to 7E:
Node number in SYSMAC NET network (1 to 126 decimal)
00 02
ICF RSV GCT D
N
A DA1 DA2 S
N
A SA1 SA2 SID
Header
Command
code
Text
00 02
ICF RSV GCT D
N
A DA1 DA2 S
N
A SA1 SA2 SID
Header
Command
code
Text
Response
code
1 0 0 0 0 0
7
6
5
4
3
2
1
0
Bit
Set to 0.
Data type (0: command; 1: response)
Response setting (0: response required;
1: response not required)
Gateway usage (0: don't use; 1: use); set to 1.
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......