![background image](http://html.mh-extra.com/html/omron/sysmac-3g8f7-clk12-ev1/sysmac-3g8f7-clk12-ev1_operation-manual_1633421040.webp)
20
Specifications and Configurations
Section 1-2
1-2-6
Indicators
Note
1. The P/S indicator is mounted to the Optical Ring Units only.
2. The TER indicator is mounted to the Wired Units only.
1-2-7
Product Components
Note
1. The following software is supplied on the CD-ROM.
• FinsGateway Version 2003 (PCI-CLK Edition)
• FinsGateway Version 3 (PCI-CLK Edition)
Name
Color
Status
Explanation
RUN
Operating
Green
Lit
The Board is operating normally.
Not lit
A Board operating error (watchdog timer error) has occurred.
ERR
Error
Red
Lit
One of the following errors has occurred.
Communications error
Node address setting error (duplicate setting)
Optical system connection error
EEPROM error
Hardware error
Data link table error
Routing table error
Network parameter error
Not lit
Operating normally (no errors in the setting tables).
INS
Participating in
network
Yellow Lit
Participating in network.
Not lit
Not participating in network.
LNK
Sending data
link
Yellow Lit
Sending data link (participating in data link)
Flashing Error in the data link table settings.
Not lit
Data link is stopped or Unit is not participating in data link.
PS (See
note 1.)
Power supply
ON
Green
Lit
Backup power supply is ON.
Not lit
Backup power supply is OFF.
TER
(See
note 2.)
Terminating
resistance set-
ting
Yellow Lit
Terminating resistance switch is ON (resistance is connected).
Not lit
Terminating resistance switch is OFF (resistance is not connected).
Optical Ring System
(H-PCF Cable and GI Cable)
Wired System
System
Model
Contents
Wired system
3G8F7-CLK23-E
3G8F7-CLK21-EV1
Controller Link Support Board
×
1
CD-ROM
×
1
Installation guide
×
1
Communications connector
×
1
Board ID switch number/indicator label
×
1
User registration card (software license agreement)
×
1
Optical ring system,
H-PCF cable
3G8F7-CLK13-E
3G8F7-CLK12-EV1
Controller Link Support Board
×
1
CD-ROM
×
1
Installation guide
×
1
Optical cable bracket
×
1
Power supply connector
×
1
Board ID switch number/indicator label
×
1
User registration card (software license agreement)
×
1
Optical ring system,
GI cable
3G8F7-CLK53-E
3G8F7-CLK52-EV1
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......