108
Commands and Responses for the Support Board
Section 6-3
6-3-13 BROADCAST TEST DATA SEND
Broadcasts test data to all nodes in a specified network.
Command Block
There is no response to this command.
The control data must be set as follows when this command is issued:
Destination node address: FF (Hex) (for broadcasting the data)
Destination unit address:
FE (Hex)
(for the Controller Link Support Board or Unit)
Response required/not required flag: 1 (response not required)
The transmission and reception status is checked by comparing the number
of times this command is issued with the
number of receptions
parameter of
the BROADCAST TEST RESULTS READ command. (For details, refer to
3-12 BROADCAST TEST RESULTS READ
6-3-14 ERROR LOG READ
Reads the PC’s error log.
Command Block
Response Block
Parameters
Beginning record no. (command):
Specifies the first record to be read, in
two bytes (four digits) in hexadecimal. (The first record number is 0000 in
hexadecimal).
No. of records (command and response):
Specifies the number of records
to be read, within a range of 0001 to 0027 in hexadecimal (decimal: 1 to 39).
Max. no. of stored records (response):
Specifies the maximum number of
records that can be recorded, within a range of 0001 to 0040 in hexadecimal
(decimal: 1 to 64).
No. of stored records (response):
The number of records that have been
recorded by the time the command is executed.
Error log data (response):
The specified error log records are returned in
sequence starting from the beginning record number. The total number of
bytes required is calculated as follows:
No. of records
×
10 bytes
Command
code
Test data
2,000 bytes
max.
08
03
Command
code
02
21
Beginning
record no.
N
o. of
records
02
21
Max. no. of
stored records
N
o. of
stored
records
N
o. of
records
Error log
data
Error log
data
Response
code
Command
code
10 bytes
10 bytes
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......