Troubleshooting Using Indicators
Section 9-1
Not lit Not lit Not lit ---
Power is not being supplied correctly to
the computer.
Check the power supply voltage and sup-
ply at the recommended voltage.
The Controller Link Support Board has
become loose.
Secure the Controller Link Support Board
firmly.
The Controller Link Support Board is
mounted in the wrong slot.
Refer to the
Installation Guide
and mount
the Board correctly.
The Controller Link Support Board is
faulty.
If the indicators do not light when the
Board is mounted in another computer,
replace the Controller Link Support Board.
Lit
Lit
Not lit 0211 Hex
The same node address is being used by
two different Units.
Reset so that each node address is used
only once within the same Network.
The Board is connected to a SYSMAC
LINK network.
Check the networks and correct the cable
connections.
Lit
Lit
---
021A Hex
Routing table setting error.
Reset the routing table correctly, referring
to
When no
routing table is being used, delete the
routing table.
There is an error in the data link table set-
tings.
When using data links, refer to
and correct the tables. When
not using data links, delete the tables.
EEPROM error
9-2 Status Information and Trou-
, correct the data where the
error has occurred, and reset the Board. If
the error occurs again, replace the Con-
troller Link Support Board.
Lit
---
Not lit ---
Cables are not connected correctly.
Check the cable connections and recon-
nect correctly.
021A Hex
The node address is larger than the maxi-
mum node address set for the network
parameters.
Either reset the maximum node address
using the Controller Link Support Software
or reset the node address to below the
maximum.
---
No other nodes exist.
Make sure that 2 or more nodes exist
within the Network.
---
No node has been set as a polling node.
Refer to
Installation Guide
and set at least
one polling node.
(A Controller Link Support Board should
normally be set as the polling node.)
Indicators
Error
history
Probable cause
Probable remedy
RUN ERR
INS
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......