150
Error Log
Section 9-3
0101
Hex
Transmission failed; local node
not in Network
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Refer to
and place the local node
into Network.
No
0103
Hex
Transmission failed; retry count
exceeded
Using the Controller Link Support
Software or FINS commands, run
echoback test and check operating
environment if errors occur.
No
0104
Hex
Transmission failed; maximum
number of frames exceeded.
Check event status on the network.
Reduce the number of events per
communications cycle or increase
the maximum number of network
parameter frames.
No
0105
Hex
Transmission failed; node
address incorrect
Refer to the
Installation Guide
and
check node address settings to be
sure they are within range and
unique.
No
0106
Hex
Transmission failed; redundant
node address
Correct node addresses so that they
are unique within the same Network.
No
0107
Hex
Transmission failed; destination
node not in Network
Refer to
node into Network.
No
0108
Hex
Unit missing; cannot execute.
Refer to the
Installation Guide
and
check the Controller Link unit num-
ber.
No
0109
Hex
Transmission failed; destination
busy
Increase number of retries or recon-
figure system to distribute load.
No
010A
Hex
Transmission failed; communi-
cations controller error
Conduct an echoback test and if the
effects of noise are considerable,
reconsider the operating environ-
ment. Restart the computer. If the
error occurs again, replace the
Board.
Yes
010B
Hex
CPU Unit error; cannot send.
Refer to the manuals for the CPU
Unit and correct the problem. If the
problem cannot be corrected,
replace the CPU Unit.
No
010C
Hex
Unit number setting error; cannot
send.
Refer to the
Installation Guide
and
check node address settings to be
sure they are within range and
unique.
No
Error
code
Contents
Detail code
Correction
Recorded
in
EEPROM
1st byte
2nd byte
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......