Applications Precautions
Section 1-4
Message Service
Procedure
1,2,3...
1. Create routing tables using the Controller Link Support Software or the Fin-
sGateway utilities, and transfer the tables to the Board.
Note
When the data link tables and routing tables are transferred to the
Controller Link Support Board, they are save in backup memory
(EEPROM) on the Board. It is not necessary to set the data again
when the power is turned OFF and ON.
2. Send and receive FINS messages using the utility applications that use the
C Library.
1-4
Applications Precautions
Board ID Switch
If more than one Controller Link Support Board is mounted to a computer,
make sure that the same Board IDs is not set for more than one Board. Up to
4 Boards can be mounted.
Note
Refer to the
Controller Link Support Board Installation Guide
(W467).
Terminating Resistance
Switch (Wired Systems
Only)
Turn ON the terminating resistance switch only for the nodes at both ends of a
wired Controller Link Network and turn OFF the switch for all other nodes.
Note
Refer to the
Controller Link Support Board Installation Guide
(W467).
Cables
Turn OFF the power of all the nodes on the network before connecting or dis-
connecting a cable.
Note
.
Use the specified cable only.
Note
1-2 Specifications and Configurations
.
Baud Rates (Wired
Systems Only)
Set the same baud rate for all nodes on the same network.
Note
Refer to the
Controller Link Support Board Installation Guide
(W467).
Routing Tables
When a CV-series PC is connected to the network, set routing tables at all the
nodes.
Note
Routing tables are not required if all the CV-series CPU Units in the Controller
Link Network have been manufactured on or after May 1996. The manufactur-
ing date can be determined from the four-digit lot number on the side of the
CPU Unit.
Set routing tables at all the nodes in all the networks when multiple networks
are connected to one PC.
Note
SECTION 7 Network Interconnections
When a routing table is transferred (written) to a PC, all CPU Bus and Com-
munications Units are reset. The routing tables must not be transferred to a
PC while the system is running.
Data Links
When using a manually set data link, delete the data link tables from all nodes
not participating in the data link.
Lot
N
o.:
@
@
5 6 . . . . Manufactured in May 1996
Indicates the last digit of the manufacturing
year. In this example, the year is 1996.
Indicates the month of manufacture. October,
N
o
v
ember, and December are indicated by x, y,
and z respecti
v
ely. In this example, the month is
May.
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......