Error Log
Section 9-3
4.
Error Status
The status of each bit indicates that an error has occurred as given in the
diagram below.
Note
If the data link tables have not been set, event ID97 will be logged in the event
log. Event ID97 indicates that a type of event memory not supported by Fins-
Gateway was set for data link data transfer, making data transfer between the
Support Board and event memory impossible. (ID97 is logged when data link
tables are not set.)
Event ID97 will no longer be logged if the data link tables are set. If data links
are not being used, operation should be normal and this event can be
ignored.
5. Ring Status
9-3-3
Reading and Clearing Error Logs
Error logs can be read or cleared using the FinsGateway, Controller Link Sup-
port Software, CX-Programmer, PC Programming Devices, or the message
service. The following examples are for the Controller Link Support Software
and the message service. When using other Programming Devices, refer to
the Programming Device’s operation manual for details.
1: Token timeout error
1: Polling timeout error
1: Communications controller hardware error
1: Polling node was changed
1:
N
odes in
N
etwork changed (added or remo
v
ed)
1: Communications controller send error
1: Duplicate node address setting error
7 6 5 4 3 2 1 0
Disconnected
node
information 1
(See note.)
Disconnection Direction Flag
0: SL1 (upstream)/
N
ormal
1: SL2 (downstream)
Disconnected
N
ode Address
(2-digit hexadecimal (00:
N
o
disconnection information))
Disconnection Direction Flag
0: SL1 (upstream)/
N
ormal
1: SL2 (downstream)
Disconnected
N
ode Address
(2-digit hexadecimal (00:
N
o
disconnection information))
N
etwork Disconnected Flag
0:
N
ormal
1: Disconnected
Local
N
ode Disconnected Flag (See note.)
0:
N
ormal
1: Disconnected
Disconnected
node
information 2
(See note.)
Note
Valid only when bit 15 (
N
etwork Disconnected Flag) is O
N
.
The pre
v
ious information will be maintained for the Local
N
ode Disconnected Flag and the Disconnected
N
ode
Information e
v
en if bit 15 is OFF (normal).
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......