151
Error Log
Section 9-3
010D
Hex
Transmission failed; destination
address incorrect
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Check routing tables.
No
010E
Hex
Transmission failed; routing
tables not registered
No
010F
Hex
Transmission failed; routing
table error
No
0110
Hex
Transmission failed; too many
relay points
Check routing tables and system
configuration. Do not try to access
Networks separated by more than
one other Network.
No
0111
Hex
Transmission failed; command
packet too long
Be sure to use the correct FINS
command format.
No
0112
Hex
Transmission failed; header
error.
No
0113
Hex
I/O setting error; cannot send.
Correct either the system configura-
tion or the registered I/O tables.
No
0114
Hex
CPU bus error; cannot send.
Check the Board and cable connec-
tions and clear the error.
No
0115
Hex
I/O duplication; cannot send.
Check the unit numbers to be sure
the same number is not set twice in
the same PC.
No
0116
Hex
CPU Bus Unit error; cannot
send.
Check the Board and cable connec-
tions and clear the error.
No
0117
Hex
Internal buffer full
Increase number of retries or recon-
figure system to distribute load.
No
0118
Hex
Illegal packet discarded
Check for nodes sending illegal
data.
Yes
0124
Hex
Maximum frame length
exceeded; cannot route.
Correct the FINS command format.
Also, be sure that the parameters
specified for the command do not
produce a response that is too long.
No
0203
Hex
EEPROM error
01 Hex:
Read error
02: Hex:
Write error
01 Hex:
Data link
tables
02 Hex: Net-
work param-
eters
03 Hex:
Routing
tables
Reset the relevant data. If the error
occurs again replace the Controller
Link Support Board.
Yes
0206
Hex
Number of participating nodes
decreased (local node still partic-
ipating)
Network
parameters
maximum
node
address
Number of
non-partici-
pating nodes
Check network parameters, node
participation, cables, and terminating
resistance.
No (See
note 3.)
0207
Hex
Number of participating nodes
decreased (local node not partic-
ipating)
No (See
note 3.)
0208
Hex
polling node changed
Address of
previous
polling node
Address of
new polling
node
Check previous polling node.
No (See
note 3.)
0209
Hex
Network parameter disagree-
ment
00 Hex
Address of
polling node
Using the Controller Link Support
Software, check network parame-
ters.
Yes
020C
Hex
Time out with token
00 Hex
Error status
(See note 4.)
Check network parameters, node
participation, cables, and terminating
resistance.
No
0210
Hex
Communications controller
transmitter error
00 Hex
Replace the Controller Link Support
Board.
Yes
Error
code
Contents
Detail code
Correction
Recorded
in
EEPROM
1st byte
2nd byte
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......