152
Error Log
Section 9-3
Note
1. Errors indicated by error codes 0101 to 0116 are recorded only when the
frame was discarded because transmission was impossible.
2. Error codes 021E to 0223 Hex are recorded only for Optical Ring Net-
works.
3. Recorded in EEPROM for the 3G8F7-CLK13-E, 3G8F7-CLK23-E, and
3G8F7-CLK53-E.
0211
Hex
Duplicate node address error
(connected to SYSMAC LINK by
mistake)
00 Hex
Local node
address
Reset so that each node address is
used only once within the same Net-
work.
No (See
note 3.)
0214
Hex
Node address setting error
Not set
Correct the node address setting.
Yes
0216
Hex
Backup power supply error
00 Hex
Error type
01 Hex: OFF
to ON
02 Hex: OFF
to ON
Check the backup power supply and
the power supply cables.
Yes
021A
Hex
Set table logic error
00 Hex
01 Hex: Net-
work param-
eters
02 Hex:
Data link
tables
03 Hex:
Routing
tables
Reset the appropriate data.
Yes
021B
Hex
Hardware error
00 Hex:
SL1 error
01 Hex:
SL2 error
Error status
(See note 4.)
Replace the Controller Link Support
Board.
No (See
note 3.)
021C
Hex
Data link error stopped
Not set
Stop the user application, reset the
computer, and retry.
Yes
021E
Hex
Network line disconnection
Ring status (See note 5.)
Refer to information in previous sec-
tions of this manual.
Yes
0220
Hex
Additional information 1 for num-
ber of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 1 to 16
Check the network parameters, the
disconnected node, and the cables.
No (See
note 3.)
0221
Hex
Additional information 2 for num-
ber of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 17 to
32
No (See
note 3.)
0222
Hex
Additional information 3 for num-
ber of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 33 to
48
No (See
note 3.)
0223
Hex
Additional information 4 for num-
ber of participating nodes
decreased (0206 Hex)
Bits 00 to 15 correspond to
disconnected nodes 49 to
62
No (See
note 3.)
0300
Hex
Packet discarded
Not set
Conduct an echoback test and find
the cause of the error.
Yes
0601
Hex
Unit error
Not set
Check the operating environment.
Yes
Error
code
Contents
Detail code
Correction
Recorded
in
EEPROM
1st byte
2nd byte
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......