111
Response Codes
Section 6-4
Example 1
In this example, data cannot be transferred between Controller Link Units due
to some cause such as a routing table error.
Example 2
In this example, the specified destination node or the next relay node does not
exist.
If an error occurs, check the MRES and SRES codes for the node in question,
and correct the problem.
6-4-3
Response Codes and Troubleshooting
The table below lists response codes (main and sub-codes) returned after
execution of the FINS commands, the probable cause of errors, and recom-
mended remedies.
Upon receipt of some commands, the destination node will issue a request to
another node; the other node is referred to as the third node.
Transmission
Computer
Controller Link Unit
Controller Link Unit
Controller Link Support Board
Response
Transmission
Controller Link Unit
Controller Link Unit
Controller Link Support Board
Response
Computer
Main code
Sub-
code
Probable cause
Remedy
00: Normal completion
00
---
---
01
Service was interrupted
Check the contents of the destination trans-
mission area of third node.
Check the data link status.
01: Source node error
01
Source node not part of Network
Add to Network.
02
Token time-out, node address too large Set the source node’s node address below
the maximum node address.
03
Number of transmit retries exceeded
Check communications with echoback test.
If the test fails, check network.
04
Maximum number of frames exceeded Either check the execution of events in the
network and reduce the number of events
occurring in one cycle, or increase the max-
imum number of frames.
05
Node address setting error (range)
Correct the node address so that it is within
specified range and that there are no node
addresses that are set twice.
06
Node address duplication error
Make sure that there are no node
addresses that are set twice.
Summary of Contents for SYSMAC 3G8F7-CLK12-EV1
Page 2: ......
Page 4: ...iv ...
Page 20: ...xx Conformance to EC Directives 6 ...
Page 48: ...28 Applications Precautions Section 1 4 Example CX Programmer Response Timeout Setting ...
Page 68: ...48 Backup Power Supply Wiring Optical Ring Systems Only Section 2 4 ...
Page 74: ...54 Using the C Library Section 3 2 ...
Page 110: ...90 Changing the Data Link Tables with Active Data Links Section 5 5 ...
Page 187: ......