16
2-1
Switch Settings
There are switches to set under the switch cover on the back of the Terminal
and also on the Host Interface Unit. For Host Interface Unit switch settings,
refer to the
Host Interface Unit Operation Manual
.
2-1-1
System DIP Switch Settings (SW1)
The 8-position DIP switch for system settings is located under the DIP switch
cover on the back of the Terminal. Be sure that power is off when changing
switch settings.
ON
SW1
1
2 3
4 5
6
7 8
Communications specification
(only for when NT600M-LK201 is mounted)
ON:
Host Link
OFF:
RS-232C
Not used.
Not used.
Mode change enable/disable
ON:
Enable
OFF:
Disable
HOST RUN input enable/disable
ON:
Disable
OFF:
Enable
Automatic reset after communications error
ON:
No automatic reset.
OFF:
Automatic reset.
Reserved for system use. (Always keep ON.)
Bit designation for lamps/touch switches
ON:
0 to 63
OFF:
0 to 111
(The settings at the time of shipping
are as shown on the left.)
Switch Settings
Section 2-1