35
Error Messages
When there is an error in screen data registered in the NT600M, the System
Menu will appear before entering RUN Mode, and the error message will be
displayed on the bottom line.
Transmit Mode
Maintenance Mode
Expansion Mode
System Menu
Quit
Screen Data Corrupted
Example of error message
V1.x
Version no.
There are three types of error messages, as shown below. If an error mes-
sage is displayed, first initialize the screen data memory before re-transmit-
ting the data. Operation will not begin again until the error has been cor-
rected.
Error message
Error Content and Correction
Screen Data Corrupted
This is displayed when registered screen data is corrupted. Initialize the screen data and
then re-register it. Operation will not begin again until the data is restored.
Mark Data Corrupted
This is displayed when registered mark data is corrupted. Initialize the screen data and
transfer the screen data files. The mark data is included in the screen data files. Re-register
the mark data. Operation will not begin again until the data is restored.
Memory Not Formatted
This is displayed when the screen data area is not formatted. Initialize the screen data
memory. All registered screen data, mark data, and system data will be deleted by the
initialization, so they will have to be transferred again from the Support Tool. In addition, if
an IC socket-type Screen Data Memory Board is being used, recheck the socket’s memory
and its settings.
3-3
Transferring Data to and from the Support Tool
Data can be transferred back and forth between the NT600M and the Sup-
port Tool. Transfer the screen data created by the Support Tool before oper-
ating the NT600M.
Procedure
Use the following procedure to transfer data.
1, 2, 3...
1.
Connect the NT600M and personal computer running the Support Tool.
2.
Select Transmit Mode from the System Menu.
System Menu
Refer to
3-1 Powering Up
.
Select “Transmit Mode.”
3.
At the NT600M, it is only necessary to place the NT600M in Transmit
Mode. The direction of transmission and the contents of the data to be
transmitted are set at the Support Tool. (For instructions on operating
the Support Tool, refer to the
NT-series Support Tool Operation Manual
.
Transferring Data to and from the Support Tool
Section 3-3
Summary of Contents for NT600M Series
Page 1: ...NT600M Programmable Terminal Operation Manual Revised October 1997 ...
Page 2: ...iv ...
Page 4: ...vi ...