12
Host Link Interface
Using the NT600M-LK201 Host Interface Unit, the Programmable Terminal
can be connected one-to-one to a Host Link Unit mounted to a Program-
mable Controller.
Host Link Unit
Mini H-type, C200H, C500, C1000H, C2000H PC
RS-232C
15 m max.
NT600M with
NT600M-LK201
SYSMAC BUS Interface
Using NT600M-RT121 Host Interface Units, up to 8 Programmable Terminals
can be connected to a PC through a Wired Remote I/O Master Unit.
Remote I/O
Master Unit
200 m max. (2 wire cable)
C200H, C500, C1000H, or
C2000H PC
8 Terminals max.
NT600M with
NT600M-RT121
C200H Host Interface
With an NT600M-LB122-V1 (for direct connection) Interface Unit, the inter-
face is set up simply by connecting one-to-one with C200H-CN221 Connec-
tion Cable to a C200H CPU Rack or Expansion I/O Rack. It is also possible
to connect a PT to a C20H, C28H, C40H, or C60H CPU Unit or I/O Units. Be
sure to use a noise filter when connecting C
jj
H. Refer to the
Host Interface
Units Operation Manual
for details.
Be sure to use a noise filter (TDK’s ZGB2202-O1U or equivalent) when con-
necting to the Mini H-type PC.
1, 2, 3...
1.
The noise filter must be inserted into the power line of the Mini H-type
PC.
2.
The distance between the noise filter and the Mini H-type PC must be as
short as possible.
3.
Keep the noise filter away from high-tension lines.
4.
The case of the noise filter must be grounded to the FG terminal of the
Mini H-type PC.
Noise filter
1
2
4
3
IN
OUT
+
--
24 V
24 V
System Configuration
Section 1-6