87
Appendix B
Specifications
General Specifications
Item
Specifications
Power supply voltage
100 to 240 VAC
Allowable power supply volt-
age range
85 to 264 VAC, 50/60 Hz
Power consumption
40 VA max.
Insulating resistance
Between AC terminal block and GR:
20 M
W
min. (at 500 VDC)
Dielectric strength
Between AC terminal block and GR:
2,300 VAC at 50/60 Hz for 1 min
Leakage current: 0.8 mA max.
Noise resistance
1000 VAC
p-p
Pulse width:
100 ns to 1
m
s
Pulse rise time: 1 ns
Vibration resistance
NT600M-DT/DF-122:
10 Hz to 22 Hz with 1.5-mm double amplitude in X,Y, and Z directions
22 Hz to 500 Hz (1.5 G; 14.7 m/s
2
) in X,Y, and Z directions for 30 min total
NT600M-DT/DN211:
10 Hz to 50 Hz with 0.5-mm single amplitude (acceleration: 2.0 G; 19.6 m/s
2
) in X,Y, and
Z directions for 1 hr each
Shock resistance
Destruction: 30G (294 m/s
2
) 3 times each in X, Y, and Z directions
Malfunction: 20G (196 m/s
2
) 3 times each in X, Y, and Z directions
Ambient operating tempera-
ture
NT600M-DT/DF-122: 5
°
C to 40
°
C
NT600M-DT/DN211: 0
°
C to 50
°
C
Ambient operating humidity
35% to 85% (with no condensation)
Operating environment
No corrosive gas
Storage temperature
NT600M-DT/DF-122: --20
°
C to 60
°
C
NT600M-DT/DN211: --20
°
C to 70
°
C
Enclosure ratings
Front control panel IP52 (Drip-proof when dust cover is installed.)
Rear case
IP20
Terminal section
IP00
Weight
Approx. 3 kg
Dimensions
NT600M-DT122/DT211/DN211: 325 x 198 x 105 (WxHxD)
NT600M-DF122: 325 x 238 x 105 (WxHxD)
(These dimensions do not include the cable.)