25
2-5
Wiring and Connectors
2-5-1
Terminal Block
The terminal block shown in the following illustration is located on the PT’s
rear panel.
HOST
RUN
INPUT
ALARM
OUTPUT
LG
GR
100 to 240 VAC
50/60 Hz
Terminal screws: M4
Use crimp-style terminals for wiring. If twisted wires are connected directly,
there is a possibility of poor contact or short-circuiting. Use crimp-style termi-
nals with holes to match M3.5 screws.
7 mm max.
Fork-type
8 mm max.
Round-type
Recommended Crimp-style Terminals
Maker
Fork-type
Round-type
Conforming wire (twisted)
Japan Solderless Terminal MFG
2-YS3A
2-3.5
1.04 to 2.63 mm
2
Fuji Terminals
2-YAS3.5
V2-S3.5
Nichifu Terminals
2Y-3.5
2-3.5
2-5-2
AC INPUT Terminals
These terminals are the power supply input terminals to run the NT600M.
MCCB
100 to 240 VAC
50/60 Hz
Insulated
transformer
Power Supply Wiring
•
Provide a 100 to 240 VAC power.
•
Use a power supply within the allowable voltage range.
Power supply voltage
Allowable voltage range
100 to 240 VAC
85 to 264 VAC
Wiring and Connectors
Section 2-5
Summary of Contents for NT600M Series
Page 1: ...NT600M Programmable Terminal Operation Manual Revised October 1997 ...
Page 2: ...iv ...
Page 4: ...vi ...