CT SB2 User Manual
26
2. In the
CT-Object
card, specify the CT data according to the CT’s name plate.
Specify the data in the order of the following table.
For more detailed information, please refer to section 6.1 on page 36.
Figure 4-1
CT-Object
card with soft keys for predefined CT ratios if the
number of taps is set to 5
Standard
Standard to be used for the CT test and the test assessment.
P/M
CT type. Set "P" for a protection CT or "M" for a metering CT.
I-pn
I-sn
Rated primary current
for the full tap combination
of the
CT and rated secondary current of the CT.
Note:
The CT data for the full tap combination can only be set
in the
CT-Object
card.
If the selected standard is IEEE C57.13 and the "Number of
Taps" is set to 5 or 3 in the
MR-Config.
card, the
CT Analyzer
offers soft keys with predefined ratios when the
"I-pn" field is selected with the cursor (see Figure 4-1). If you
select one of these predefined multi-ratio schemes, the
CT Analyzer
automatically specifies the ratios for all tap
combinations in the
MR-Config.
card.
Note:
The default number of taps can be set in the device
settings of the
CT Analyzer
, see chapter 5 on page 33.
If the selected standard is not IEEE C57.13, enter the values
for I
pn
and I
sn
manually.
Class
Rated accuracy class of the CT. This field becomes available
after selecting the CT type (protection or metering CT).
VA (or Vb)
cos
ϕ
Nominal burden
for the full tap combination
of the CT.
For protection CTs of the IEEE C57.13 classes C, K and T,
enter the rated secondary terminal voltage V
b
instead of VA.
The
CT Analyzer
then automatically calculates the value for
VA.
The cos
ϕ
for the nominal burden is automatically selected
according to the standard.
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...