CT SB2 User Manual
36
6.1
CT-Object Card for Multi-Ratio CT Testing
Use the
CT-Object
card to specify the CT data according to the CT’s name
plate. Specify the data in the order of the following table.
Figure 6-1
CT-Object
card with name plate data entered
Standard
Standard to be used for the CT test and the test assessment.
P/M
CT type. Set "P" for a protection CT or "M" for a metering CT.
I-pn
I-sn
Rated primary current
for the full tap combination
of the
CT and rated secondary current of the CT.
These values specify the full tap ratio displayed in the
MR-Config.
card. The full tap ratio of the CT can only be
specified and/or changed here.
For IEEE C57.13 only:
If the selected standard is IEEE C57.13 and the "Number of
Taps" is set to 3 or 5 in the
MR-Config.
card, the
CT Analyzer
offers soft keys with predefined ratios for 3-tap
or 5-tap CTs when the "I-pn" field is selected with the cursor
(see Figure 6-2).
If you select one of these predefined multi-ratio schemes, the
CT Analyzer
automatically specifies the ratios for all tap
combinations in the
MR-Config.
card. For example, selecting
the
1200 : 5 A
soft key will result in nominal ratios of
1200 : 5, 800 : 5, 300 : 5 and 200 : 5 (see Figure 6-3 on page
38).
Note:
Selecting a predefined multi-ratio scheme overwrites
possibly existing settings for I
pn
and I
sn
in the
CT-Object
card
and the ratios in the
MR-Config.
card.
Class
Rated accuracy class of the CT. This field becomes available
after selecting the CT type (protection CT or metering CT).
Fields underlined by dotted lines can be edited.
In multi-ratio test mode, the status line displays the
full tap combination of the CT.
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...