CT Analyzer User Manual
40
3. Connect the red "Output" socket and the red socket of input "Sec" of the
CT Analyzer
to the other (ungrounded) side of the burden.
Figure 2-18
Wiring for a polarity check of the burden wiring using
Quick Test
and the
CPOL
polarity checker
Note:
The
CT Analyzer
measures the voltage of the injected signal using input
"Sec". Therefore, you should always connect this input when using the Polarity
Check measurement type. The higher the resistance of the wiring checked (i.e.,
the burden wiring) or the current amplitude set on the
CT Analyzer
, the higher
the terminal voltage generated by this current!
CT
Burden
CPOL
CPOL
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...